System Rating(kVA) |
10 |
15/20 |
30 |
40/50 |
60 |
100/120 |
160 |
200 |
Mains Input |
Input Supply |
415 VAC , 50 Hz (-20%, +15%),3 Phase 4 Wire |
Battery |
Battery Voltage |
240 V DC |
360 V DC |
480 V DC |
Inverter |
Power in KW |
8 |
12/16 |
24 |
32/40 |
48 |
80/96 |
128 |
160 |
Switching Element |
IGBT |
Control |
32 Bit DSP controlled |
Nominal Output Voltage |
415 VAC L - L, 3 Phase 4 Wire |
Nominal Frequency |
50 Hz |
Output Waveform |
Sine Wave |
Output THDv |
< 3% non-linear |
Phase unbalance |
< 1deg |
Load Power Factor |
0.6 lag to 1 (within kVA and kW rating) |
Voltage regulation |
± 2% |
Voltage Stability in dynamic condition |
Complies with IEC/EN 62040-3, Class 1 |
Output voltage distortion with 100% linear load |
< 2% |
Inverter efficiency |
Up to 90% |
Up to 93% |
Up to 94% |
Protection degree |
IP 20 |
Colour |
RAL 7016, Texture |
Cooling |
Forced Air |
Galvanic Isolation |
Inbuilt isolation transformer at inverter output |
Protection |
Under / Over voltage for Input, Output & Battery |
|
Output overload, Short circuit, Over temperature |
Display Parameter |
1. Battery - Voltage, Current |
|
2. Mains - Voltage, Current |
|
3. Inverter - Voltage, Current, Inv. heat sink temp., Power |
Indications |
Battery on Float, Battery on Boost, Battery low, Battery Charging / Discharging, |
|
Mains Switch ON, Inverter Switch ON, Mains ON, Load ON, Inverter ON, Manual Bypass ON |
Environment |
|
Temperature Operating |
0 to 40° C |
Max. Relative humidity @ 25°C (non condensing) |
Up to 95% |
Acoustic Noise @ 1m (Ref. ISO 3746) |
≤ 62 dBA |
≤ 65 dBA |
≤ 68 dBA |
Max. Altitude above sea level without de-rating |
1000 m |
Standard Compliance |
|
Enclosure Protection Grade |
IP 20 |
Testing |
IEC 62040 - 3 |